[technical analysis] causes of high surface temperature of water cooled condenser

visits:57 addtime:2023-10-11 16:37:33

n the working process of the refrigeration system, the temperature of the outer surface of the water-cooled stage condenser should be close to the normal temperature, and the hands should not feel hot. Once the surface temperature is too high, the cause should be found out and measures should be taken to eliminate this phenomenon.


Generally speaking, the main cause of condenser temperature rise is the problem of cooling water. There are usually four kinds of feelings


Situation:


1) There is not enough cooling water and water pressure. The water-cooled condenser uses cooling water to take away the latent heat released during the condensation of refrigerant vapor. Therefore, the pressure of cooling water is not enough, the flow rate can not meet the rated requirements, and the heat dissipation capacity is limited, * which eventually causes the surface temperature of the condenser to rise.


2) The cooling water temperature is too high, which is higher than the rated operating temperature (usually 32 ℃). The cooling water temperature in Vietnam, the smaller the cooling temperature difference of refrigerant, the smaller the heat transfer, the refrigerant can not be effectively cooled, and the surface temperature of condenser will rise


High.


3) The poor quality of cooling water leads to scaling on the inner wall of the cooling water pipe in the condenser, increasing the thermal resistance, affecting the heat exchange between refrigerant and cooling water, and reducing the heat transfer effect. This kind of fault often occurs in the equipment which has been used for a long time and has not been cleaned regularly. The solution is to remove scale.


4) The inlet and outlet pipes of cooling water are installed incorrectly. The normal installation position is generally low inlet pipe position and high outlet pipe position


"Low in, high out.". If the inlet pipe is set high, the cooling water can not be completely filled in the condenser, the heat transfer area will be smaller, and the refrigerant vapor can not be effectively condensed, which will make the surface temperature of the condenser rise.


When the surface temperature of the condenser increases, it means that the condensation effect is recommended, and the cooling capacity of the system will decrease.


主站蜘蛛池模板: 亚洲AV无码久久三宫椿系列 | 亚洲人成无码网WWW动漫 | 少妇粗大进出白浆嘿嘿视频 | 国产精品超清白人精品AV | 夜精品a片一区二区无码 | 天堂网在线.www天堂 | 少妇富婆高级按摩出水高潮 | 少妇的丰满2中文字幕 | 无码一区二区三区免费 | 强奷乱码欧妇女中文字幕熟女 | 乌克兰粉嫩xxx极品hd | 精品久久8X国产免费观看 | 国产福利一区二区精品秒拍 | 四虎影视214HU永久免费观看 | 亚洲AV中文无码4区 亚洲中文字幕无码日韩精品 | 日本免费一区二区三区四区五区 | 亚洲综合另类小说色区 | 国产av无码专区亚洲av软件 | 日木AV无码专区亚洲AV毛片 | 波多野结衣视频在线播放 | 把腿张开老子CAO烂你动态图 | 免费看荫蒂添的好舒服视频 | 日韩爱爱爱 | 全免费A级毛片免费看无码 狠狠操狠狠插 | 日本高清免费aaaaa大片视频 | 中午字幕在线 | 理伦少妇片一级 | 午夜黄大色黄大片美女 | 无码爆乳护士让我爽 | 办公室扒开奶罩揉吮奶头视频 | 手机看黄AV免费网址 | 亚洲av不卡一区二区三区 | 夜夜爽妓女8888视频免费观看 | 国产亚洲人成无码网在线观看 | 亚洲一区二区三区中文字幕无码 | 国产精成A品人V在线播放 | 无码专区—va亚洲v专区 | 亚洲国产成人AV毛片大全 | 国产成人无码www免费视频播放 | 国产亚洲日韩一区二区三区 | 欧美日韩免费 |